2024年3月27日发(作者:)

伟肯变频器参数VACON 45KW 500V

1 Basic Parameters

1.1 Min Frequency

1.2 Max Frequency

1.3 Accel Time 1

1.4 Decel Time 2

1.5 Multi Step1

1.6 Multi Step2

1.7 Current Limit

1.8 U/f Ratio Select

1.9 U/f Optimization

1.10 Output Max Volta

1.11 Motor Nom Freq

1.12 Motor Nom Speed

1.13 Motor Nom Currnt

1.14 Supply Voltage

1.15 Param Conceal

1.16 Parameter Lock

1.17 Basic Ref Select

2 Input Signals

2.1 Start / Stop Logic

2.2 Dia3 Function

2.3 Curr Ref Offset

2.4 Ref Scal Min Val

2.5 Ref Scal Max Val

2.6 Ref Invert

2.7 Ref Filter Time

2.8 PI P Gain

2.9 PI P Time

2.10 PI High Lim

2.11 PI Low Lim

2.12 PI Scale

3 Output Signals

3.1 Iout Content

3.2 Iout Filter Time

3.3 Iout Invert

3.4 Iout Minimum

3.5 Iout Scale

3.6 DO1 Content

3.7 RO1 Content

3.8 RO2 Content

3.9 Freq Supv Lim 1

3.10 Freq Supv Val 1

3.11 Opt Aout Invert

3.12 Opt Aout Scale

4 Drive Control

4.1 Ramp 1 Shape

0Hz

50Hz

3.0s

3.0s

10.0Hz

50.0Hz

60.0A

2 / Programmable

0 / None

500V

50Hz

1470 rpm

77.0A

17 / 500

0 / All Visible

0 / ChangeEnable

2 / Panel

3 / StartP – StopP

6 / P/Pi Selection

0 / 0-20 mA

0Hz

0Hz

0 / No Inversion

0.10s

0

0.00s

0V

0V

0%

1 / Motor Freq

1.00s

0 / No Inversion

0 / 0 mA

100%

1 / Ready

2 / Run

3 / Fault

0 / Not Used

0.0Hz

3 / MotorCurrent

100%

0.0s

4.2 Ramp 2 Shape

4.3 Accel Time 2

4.4 Decel Time 2

4.5 Brake Chopper

4.6 Start Function

4.7 Stop Function

4.8 DC-Brake Current

4.9 Stop DC-Brake t

5 Prohibit Freq

5.1 Range 1 Low Lim

5.2 Range 1 High Lim

6 Motor Control

6.1 Control Mode

6.2 Switching Freq

6.3 Field Weakn Pnt

6.4 Voltage at FWP

6.5 U/f Mid Freq

6.6 U/f Mid Voltg

6.7 Zero Freq Voltg

6.8 Overvolt Vontr

6.9 Undervolt Vontr

7 Protections

7.1 Reference Fault

7.2 External Fault

7.3 Phase Supervisn

7.4 Earth Fault

7.5 Motor Therm Prot

7.6 MTP Fnom Current

7.7 MTP F0 Current

7.8 MTP Motor T

7.9 MTP Fnom

7.10 Stall Protection

7.11 Stall Current

7.12 Stall Time Lim

7.13 Stall Freq Lim

7.14 Underload Protect

7.15 Up fnom Torque

7.16 Up f0 Torque

7.17 Up Time Limit

8 Auto Restart

8.1 Number of Trials

8.2 Trial Time

8.3 Start Function

9 UnderVoltage Con

9.1 UV Normal

9.2 UV Delta Normal

9.3 UV Expected Limi

0.0s

10.0s

10.0s

0 / No

0 / Ramping

0 / Coasting

38.5A

0.00s

0.0Hz

0.0Hz

0 / Freq Control

3.6Hz

50Hz

100%

3.0Hz

0.00%

0.00%

1 / On

1 / On

0 / No Action

0 / No Action

2 / Fault

2 / Fault

2 / Fault

100%

45%

45.0min

35Hz

1 / Warning

130%

15.0s

25Hz

0 / No Action

50.0%

10.0%

20.0%

0

30s

0 / Ramping

1111

-1000

8400