2024年4月29日发(作者:)
RA890F
Flame Safeguard
Primary Control
The RA890F Protectorelay™ Primary Control
is a nonprogramming, amplifying relay that pro-
vides solid state electronic flame safeguard pro-
tection for industrial and commercial gas, oil, or
combination gas-oil burners.
sEmploys rectification principle of electronic flame
detection using a flame rod, rectifying photocell, or
C7012A,C Ultraviolet Flame Detector.
sClipping pilot link jumper wire permits use with
standing pilots.
sCan directly replace RA890E and mount on same
Q270A Subbase.
sSolid state circuitry eliminates vacuum tube replace-
ment and increases resistance to vibration. Power
application not required during Off cycle; no tube to
warm up before starting.
sPush-to-reset safety switch in dust-resistant enclosure.
sBuilt-in protection against ignition crossover in flame
rod systems.
sDoes not start if flame-simulating failure occurs in
flame detector circuit.
sAutomatic safety shutdown if flame fails on start, or
if flame not re-established after flame failure.
sFlame signal current is directly measurable at test
jack.
sLine or 24 volt, automatic or manual controller can be
used. (Manual controller must open circuit on either
power or flame failure.)
sCaptive mounting screws allow easy mounting and
removal. Thermoplastic mounting base.
sOptional alarm circuit indicates safety shutdown.
CONTENTS
2
.2
4
7
8
.10
Troubleshooting 10
S.Y. • Rev. 11-94 • ©Honeywell Inc. 1994
1
60-2034-7
60-2034—7
RA890F
SPECIFICATIONS • ORDERING INFORMATION
Specifications
TRADELINE
®
MODELS
®
Terminal Ratings:
TRADELINE models of this device are available. They
are selected and packaged to provide ease of stocking, ease of
handling, and maximum replacement value. TRADELINE
®
model specifications are the same as those of the standard
model except as noted below.
TRADELINE
®
MODELS AVAILABLE:
RA890F for 120V, 50/60 Hz power supply.
RA890F for 240V, 50/60 Hz power supply.
ADDITIONAL FEATURES: TRADELINE
®
packed with
cross reference label and special cross reference listing.
Terminal
3
Electrical Load
Burner
Full Load
Motor
Locked
Rotor
(inrush)
Ignition
a,b
Pilot Fuel Valve
120 Vac240 Vac
5.2A
31.2A
2.6A
15.6A
3.0A
25 VA
3.0A
125 VA
1.5A
25 VA
1.5A
125 VA
4
5
a
Ignition
a
Gas Valve
b
STANDARD MODELS
MODEL: RA890F Protectorelay™ Primary Control.
ELECTRICAL RATINGS:
Voltage and Frequency: 100V, 120V, 208V, 220V, or
240V, 50/60 Hz. As ordered.
Power Consumption:
60 Hz: 7.0W maximum, 1.7W standby.
50 Hz: 8.5W maximum, 3.0W standby.
VA Ratings:
60 Hz: 13.0 VA maximum, 8.3 VA standby.
50 Hz: 17.0 VA maximum, 13.6 VA standby.
If ignition and motor are connected to terminal 3, termi-
nal 4 cannot be used. This is to prevent overloading
relay 1K.
b
Alternate Rating: 25 VA pilot duty plus one or more
motorized valves with total rating 400 VA opening,
200 VA holding.
Alarm Contacts: 3.0A at 24 Vac or 1.0A at 120 Vac in
suitable wiring enclosure.
Low Voltage Control Circuit (T-T): 0.3A.
Ordering Information
When purchasing replacement and modernization products from your TRADELINE
®
wholesaler or your distributor, refer to the
TRADELINE
®
catalog or price sheets for complete ordering number, or specify:
number (standard or TRADELINE
®
).
e and frequency.
response time.
switch timing.
contacts, if desired.
thermistor timing if desired.
ories, if desired.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
local Honeywell Home and Building Control sales office (check white pages of phone directory).
and Building Control Customer Logistics
Honeywell Inc., 1985 Douglas Drive North
Minneapolis, Minnesota 55422-4386 (612) 951-1000
In Canada—Honeywell Limited/Honeywell Limitée, 740 Ellesmere Road, Scarborough, Ontario M1P 2V9. International sales and service
offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain,