FIELD COMMUNICATOR

JIANGSU BOOST INSTRUMENT SCIENCE AND TECHNOLOGY CO.,LTD

CONTENTS

CHAPTER Ⅰ Introduction…………………………………2

CHAPTER Ⅱ Basic use…………………………………..3

2.1 Field communicator basic performance and functions………………3

2.2 Power Considerations………………………………………………..4

2.3 Key areas of use and instructions……………………………………5

CHAPTER Ⅲ menu online operation

3.1 Test menu…………………………………………………………..6

3.1.1 Always poll……………………………………………………6

3.1.2 Ask before polling……………………………………………….7

3.1.3 Select the type…………………………………………………...7

3.2 PRESS TRANS MAIN MENU………………………………………8

3.2.1 Process variables………………………………………………….8

3.2.2 Diagnostics and service………………………………………...9

3.2.3 Characterization…………………………………………………..11

3.2.4 Calibration………………………………………………………..17

3.2.5 Display mode…………………………………………………….19

3.2.6 General format…………………………………………………...20

3.3 ELECTROMAGNETIC FLOWMETER MAIN MENU…………...20

3.4 VORTEX FLOWMETER MAIN MENU…………………………..20

3.5 FARGET FLOWMETER/ FLOAT LEV GAUGE MAIN MENU….20

3.6 METAL ROTAMETER MAIN MENU……………………………..20

3.7 GENERAL MAIN MENU…………………………………………..21

CHAPTER Ⅳ Troubleshooting………………...…………21

4.1 Description and remedy fault………………………………………..21

4.2 Windows for warning………………………………………………..22

Appendix I……………………………………………………24

Appendix II…………………………………………………...25

Appendix Ⅲ…………………………………………………31

1

CHAPTER Ⅰ Introduction

Thank you for using HART475 Field Communicator,

Communicator for the HART Communication protocol smart

transmitter operation, and HART275, HART375,HART475

compatible with excellent compatibility, communication

1151,3051,EJA, ABB and flow aspects of the HART protocol

imported instruments. Completely and yung made a variety of

smart transmitters.

The manual describes the basic use of field communication

device, connection and operation in Content as well as

troubleshooting and in the course should pay attention.

Field Communicator using the HART475, please read the

manual, In order to better play to the best performance of the

product in use or maintenance of the product Before

understanding of the appropriate content.

Should the equipment needs repair, please contact our

company. We will do our best to for you.

The device is equipped with:

a manual operator

Battery a

Pack a

A charger

A communication cable

Manual a

A 250 ohm resistor

2

CHAPTER Ⅱ Basic use

2.1 Field communicator basic performance and functions

Communicate

cable

Battery

display

Display

Four

keys

navigation

PV Key

Enter

ON/OFF

Alphanumeric keypad

Left -right selection

key

Charger connector

Field Communicator

3

2.2 Power Considerations

In turn, ensure the following:

* The Field Communicator is no mechanical damage

* Battery is fully charged.

* The Field Communicator to connect to the circuit (Figure 2-2)

* String loop resistance of 250 ohms

·

·

Power —

Figure 2-2

Start Field Communicator

Before starting to ensure that the device is fully charged.

Start holding down the power key until To the bright LCD screen,

a successful boot.

Close

Such as to close the Field Communicator, hold the key to

open up their show off, shutdown complete.

4

2.3 Key areas of use and instructions

Open key

The key is used to enable or disable the Field Communicator.

Arrow navigation keys

Four navigation arrow keys provide menu options.

Press the right arrow navigation key to enter a menu of

specific options. Press Left navigation key to return to the

previous menu, up and down navigation keys can be cut

down in the menu Change. In the character input mode digital

down navigation keys can be used as a backspace key.

Enter

After entering the menu, you can modify the contents of the

LCD's bottom Line will automatically display the "Edit" to modify

the words For you press the Enter key, the change was

successful.

Alphanumeric keyboard

Character numeric keypad to enter characters, numbers and

other symbols, numbers, and he has Characters in both input

modes, field communication device according to the need to

select the appropriate input enter numbers, press the

number directly to where the keys to enter characters, according

to the word Character position on the keyboard, first press

A key, then press the character

5

key is located. For example, to enter the character "A", the first

Press the left selection key, then press the number 1

character keyboard.

PV key

Monitoring real-time variable shortcuts, view real-time

pressure, current, percentage, Temperature, frequency and

other real-time variable. Digital input mode, the character, the

key is invalid.

CHAPTER Ⅲ menu online operation

3.1 Detection menu

How to poll:

Poll

Bef Poll

Figure 3-1

3.1.1 Polling Detection

Select the menu, Field Communicator polling numbers from

the polling numbers from 0 to 15 followed by detection

equipment, if detected, the device will automatically detect the

transmitter and the station number(Figure 3-1-1), press the right

navigation key to enter the device type selection menu (Figure

6

3-1-2); if not Have detected the device does not detect the

transmitter will appear warning.

TRANS detected:

TAG No[DS8001]

Figure 3-1-1

3.1.2 Detection by poll numbers

Specified number of polling devices to detect, according to

the up and down navigation keys Choose between 0 to 15

polling numbers, then press the right navigation key to start

the test (test results If the same as Figure 3-1-1).

3.1.3 Select Device Type

1. Pressure Transmitter

2 electromagnetic flowmeter

3. Vortex Flowmeter

4. Target Flowmeter / float level gauge

5. Turn meter gold

6 General menu

Select the type:

1.PRESS TRANS

2.Electromagnetic Flow meter

3.Vortex Flowmeter

4.Target Flowmeter / Float

LEV gauge

5.Metal Rotameter

6. General Menu

Figure

3-1-2

7

When choosing the type of equipment must be selected

according to the type of field device into a specific menu, if you

select the type does not match the actual type, will cause an

error. If the site becomes non-pressure equipment,

electromagnetic, vortex, target-style, gold transfer device is

connected into the general menu. Press the down

navigation key to select the device type, then press the right

navigation key to enter the selected device type detection, and

enter the corresponding menu, if you select the type does not

match with the test will be prompted.

3.2 Pressure Transmitter Main Menu

Submenu

1 Process Variable

2 Configuration and testing

3 Characterization

4 Calibration

5 Display Modes

6 common format

3.2.1 Process Variable

Real-time display of pressure transmitter, the percentage of

current, temperature and other parameters (Figure 3-2-2). Press

the left navigation button for 3 seconds before the bounce out of

real-time variable monitoring model.

PRESS –0.258

AO 4.820

PC 5.127

TEMP 19.570

8

Main menu:

1.Process VAR

2.DIAG and Service

3.Characterization

Figure 3-2-1

Kpa

mA

%

Figure 3-2-2

3.2.2 Configuration and Testing

Submenu:

1. Equipment Testing

2. Loop test

3. Basic Settings

4. User range

3.2.2.1 Test equipment

Testing equipment status, if everything is normal, liquid

crystal display "device normal", if wrong, will be a warning.

3.2.2.2 Loop Test

Detection of the D / A current output. First, a series

ammeter in the circuit, and then type a 4-20mA current between

the values into the transmitter, the transmitter will automatically

output the current value type, if the type of value and ammeter

display values are not equal, current fine-tuning to be done.

3.2.2.3 Basic Settings

Submenu:

1. Unit

2. Write Protect

3. Damp

4. Output

5. Device Information

6. Polling numbers

Unit

9

DIAG and Service

1.Test Device

2.Loop Test

3.Basic setup

Figure 3-2-3

Basic Setup

1.Unit

2.Write Protect

3.Damping

Figure 3-2-4

Change the primary variable units and display units. Provide

MPa, Kpa, Pa, InH2O, InHg, psi, g / cm ², kg / cm ², FtH2O, torr,

ATM, mmH2O, mmHg, Bar, mBar these 15 units. When the unit

of measure on behalf of the Not recognize the number will

automatically display "No" means that the unit "unknow". Repair

Change methods, see the menu tree.

Write Protect

Read-write device protection status, when the

write-protected, the transmitter can not change the internal data.

Damp

Read-write device damping coefficient (rounded to three

decimal places). Seconds.

Output

Read-write device output. Divided into linear, square root,

and the unknown. The default is linear.

Device Information

Read and write tag number, date, descriptor, message,

final assembly number

Polling numbers

3.2.2.4 User range

User Range

rd input

e pressure

Figure 3-2-5

Keyboard input

10

Select this menu, the first prompt sensor range, then enter

the range of the setup menu, press the down navigation key to

select zero or range, then enter the user needs to set the value

(rounded to three decimal places), then press the right

navigation key into the transmitter.

Sensor Range

L –180.000KPa

H 180.000KPa

User Range

L –180.000KPa

H 180.000KPa

Figure 3-2-6 Figure 3-2-7

Provide pressure values

Pressure on the current value with the transmitter zero and

span settings, press the up and down navigation keys,

press the right navigation key to confirm.

Provide Pressure

1.Zero

2.Range

3.2.3 Characterization

Submenu:

1 .Sensor trim

2. Sensor measuring range

3 user range

4.K coefficient

5 Formatting

11

Figure 3-2-8

Characterization

1.Sensor Trim

2.Sensor range

3.User range

Figure 3-2-9

6 small-signal removal

7 Device Address

8. Data Backup

9. Data Recovery

The menu will seriously affect the operation of the

transmitter to work and accuracy, so enter this menu, you need

to enter the authentication password (Figure 3-2-10).

Please input password:

******

Figure 3-2-10

The default password is: 666666

3.2.3.1 Sensor trim

Sensor Trim

1.Zero Trim

2.Low Range Trim

3.High Range Trim

Figure 3-2-11

Zero trim

After the pressure transmitter with 0 to select this operation,

the transmitter automatically adjust zero.

Low fine-tuning

To increase low-pressure transmitter (in KPa), type the

applied pressure values (rounded to three decimal places), the

12

transmitter automatically corrected, so that the output value of

the applied pressure.

High-end fine-tuning

To the transmitter plus high pressure (in KPa), type the

applied pressure values (rounded to three decimal places), the

transmitter automatically corrected, so that the output value of

the applied pressure.

3.2.3.2 Sensor Range

Sensor Range

1.Select the range

2.Madify range

Figure 3-2-12

Select the range

First select the type of sensor, and then select the range of

the sensor code, then press the Enter key into the transmitter.

(Figure 3-2-13,3-2-14)

Sensor type

[ DP

推出

Figure 3-2-13

Range Code

[5]

推出

Figure 3-2-14

Modify Range

13

First select the range sensor code, then enter the code in the

range of the scale. Note: The input pressure is measured in Pa,

can only enter a positive integer. Change and then select the

sensor range.

3.2.3.3 User range

Keyboard input

Select this menu, the first prompt sensor range, then enter

the range of the setup menu, press the up and down

navigation key to select zero or range, then enter the user

needs to set the value (rounded to three decimal places), enter

and press the right navigation key to send into the

transmitter.

Sensor Range

L –180.000KPa

H 180.000KPa

User Range

L –180.000KPa

H 180.000KPa

Figure 3-2-15

Figure 3-2-16

Provide pressure values

Pressure on the current value with the transmitter zero and

span settings, press the up and down navigation keys,

the right navigation key to confirm.

press

Provide Pressure

1.Zero

2.Range

14

Figure3-2-17

3.2.3.4 K factor

Low-end need to be done, do high-end.

K-factor

1.Low Range

2.High Range

Figure 3-2-18

Low Range

Add 0 to the pressure transmitter, type 0 in the increase of

pressure, press the right navigation key into the transmitter, the

transmitter automatically adjust the k-factor low.

High Range

Added to the positive terminal of a pressure transmitter

(close to or equal to the physical range), the pressure increases

the pressure must be greater than 0, type in the increase of

pressure values (rounded to three decimal places, units KPa),

press the right navigation key into the transmitter device, the

transmitter automatically adjusts the k-factor high.

Note: K factors must be operated in positive pressure conditions,

and the input unit KPa.

3.2.3.5 Format

Full-scale format

Note: This action will seriously affect the accuracy of the

transmitter, the user is best not to make their own format.

15

How-to: give added pressure transmitter (pressure points must

be positive from the negative pressure up to maximum

pressure), then enter the applied pressure (Figure 3-2-19, note:

do the negative pressure side formatting , the input pressure to

a minus sign in front.), then press the right navigation key to

format it, after a successful return to the next point format, an

unsuccessful return warning.

All of range:01

PRESS:[ ]Pa

Figure 3-2-19

Interpolation

After the ultra-poor calibration point format.

Note: This action will seriously affect the accuracy of the

transmitter, the user is best not to make their own format.

How-to: give added pressure transmitter, and then enter the

increase of pressure. (Note: do the formatting in the negative

pressure side, the input pressure to a minus sign in front). Press

the right navigation key, the interpolation done at this time point

measured the pressure should be basically equal to the applied

pressure.

Interpolation

PRESS:[ ]Pa

Figure 3-2-20

3.2.3.6 Small-signal removal

16

This function is to eliminate the zero drift. Enter the

number of users than the extreme range.

3.2.3.7 Device address

View a device's address. Device address is the unique

identification number the smart board.

3.2.3.8 Data Backup

Data backup: the value of the current user scale and

format all the data back to FLASH the database, this function is

to facilitate data recovery after a mistake. Click the menu

"Backup" button

3.2.3.9 Data Recovery

Data Recovery: The instrument factory, manufacturers

have the formatting operation on the instrument, and the correct

data formatted to do a backup, misuse of the instrument when

the user does not work, you can use the "Data Recovery"

function of its error Content removal operation, and

re-manufacturers will re-initialize the backup data is written

instrument, easy instrument to restore the original data. Click

the menu "Data Recovery" button.

3.2.4 Calibration

Submenu

1 Sensor trim

2 Output Trim

3.2.4.1 Sensor trim

Sensor Trim

Trim

Range Trim

Range Trim

17

Calibration

Trim

Trim

Figure 3-2-21

Figure 3-2-22

Zero trim

After the pressure transmitter with 0 to select this operation,

the transmitter automatically adjust zero.

Low fine-tuning

To increase low-pressure transmitter (in KPa), type the

applied pressure values (rounded to three decimal places), the

transmitter automatically corrected, so that the output value of

the applied pressure.

High-end fine-tuning

To the transmitter plus high pressure (in KPa), type the

applied pressure values (rounded to three decimal places), the

transmitter automatically corrected, so that the output value of

the applied pressure.

3.2.4.2 Output Trim

Output fine-tuning needs to be a precision ammeter in series

to the circuit, into the fine-tuning, the LCD will prompt access

ammeter, the current fine-tuning exit, the LCD will prompt

recovery circuit.

Warning:

Please access circuit

ammeter!

Figure 3-2-23

4mA current fine-tuning

Choose 4mA current fine-tuning, the output should be

4.000mA, if the ammeter shows the value is not equal to

4.000mA, select "No", an input box, type the ammeter shows

18

the input box value (rounded to three decimal places), then

press right navigation key to enter the current value into the

transmitter, the transmitter will automatically calibrate the

current output, the output of 4.000mA, if a less than satisfactory

results, repeat this operation.(Note: The meter accuracy should

be higher than the output precision of the table)

Output Trim

DAC Zero

2. Trim DAC Gain

Figure 3-2-24

20mA current fine-tuning

4mA current methods of operation and fine-tuning the same.

3.2.5 Display Mode

1.%

Select this mode, the transmitter displays the percentage.

SET

Select this mode, the transmitter displays the user settings.

SET &%

Select this mode, the transmitter displays the percentage of

user settings and are displayed alternately every 4S.

PRESS

Select this mode, the transmitter only the input pressure.

PRESS &%

Select this mode, the transmitter displays the percentage of

input pressure and alternating every 4S.

19

Display Mode

1.%

2.USER SET

3. USER SET&%

Figure 3-2-25

3.2.6 General Formatting

General Format: (known as three, five-point format)

This menu requires a password to enter the default password is

666666.

(1)

Select the instrument type and range of code to determine

the instrument's physical range.

(2) in the common format into the format, the original plate for

1151 current 22mA, the order of the physical range of 0%, 60%,

100% three-point format, or 0%, 60%, 100%, -60%, 100%

five-point format. Communication device according to the first

line shows the calculation of the percentage range of physical

pressure, the pressure and the input Fill pressure (in Pa),

right-click until the pressure stabilized first sent.

(3) operation is successful, display the percentage of the next

point, to continue or exit.

Operation failed (such as the pressure increases the pressure

and display the corresponding percentage difference too large

to return to this point redo. Done 100% in three-point format

according to exit after completion of five-point format at 100%

done automatically exit. withdrawal of current from 22mA into a

measurement of current.

3.3 Electromagnetic Flowmeter Main Menu

See photos

20

3.4 Vortex Flowmeter

See photos

3.5 Target Flowmeter / float level gauge

See photos

3.6 meter gold transfer

See photos

3.7 Common main menu

See photos

Remarks:

The handheld contains vortex flowmeter, the target flowmeter,

flow meter gold turn, Common menu and menu operation is

similar to the electromagnetic flow meter, this is not setting them

in, with Please refer to the distribution of body attached page

menu menu tree operation.

CHAPTER Ⅳ Troubleshooting

4.1 Introduction and troubleshooting faults

It does not really start

If in the course can not be switched, that can not start the Field

Communicator, First check the battery. Should the battery power

is still not start, there may be on-site Communication device to

open the key is damaged. (Note: Please do not use the process

of firm Hard thing to touch the buttons Field Communicator film

to avoid damage. )

Communication or communications are not interrupted

If there is no communication on the first check HART field

device loop and voltage. Almost all field devices have at least

4mA and 12VDC to Victoria maintain normal operation.

21

Check the loop impedance, to see whether the access loop

250 ohm external Impedance. Access to 250 ohm resistors, will

lead 250 ohm resistor at both ends of the access. And then view

the communication is normal.

Check the terminal and HART communications cable is

damaged.

HART communication by the control system interference.

At this point stop control system HART communication,

recognition and communication between the field device

communication.

4.2 Tips interface

Low battery warning

When the battery voltage is low, top right of the LCD display

will flash a battery-shaped pattern.

TAG No(DS8001)

Online

PRESS 0.006 Kpa

AO 4.000 mA

Figure 4-2-1

Communication Failure Warning

When the Field Communicator to the transmitter with the

communication failure warning (Figure 4-2-2).

22

Warning:

Communication interruption!

Check the equipment

Figure 4-2-2

Date Input Error

Allows you to enter a date range January 1, 1900 to

December 31, 2155, when the input is not in the range of dates,

enter the error message will appear (Figure 4-2-3), note the

date input format xxxx xx xx day in May.

Date entered incorrectly

Figure 4-2-3

Data entry errors

When the input parameter is incorrect when the prompt

appears, such as the removal of only a small signal input is an

integer, if you enter a negative number, an error message will

appear (Figure 4-2-4).

Entered incorrectly!

Figure 423-2-4

Appendix I: General menu list of unit types

No.

1

5

9

13

17

21

25

29

33

37

41

45

49

53

57

61

65

69

Unit

InH2O

psi

kg/cm2

ATM

L/S

Ω

m3

min

v

lb

g/min

kg/h

lb/min

LT/h

kg/l

L/h

KJ

GJ

No.

2

6

10

14

18

22

26

30

34

38

42

46

50

54

58

62

66

70

Unit

InHg

bar

Pa

L/min

m3/s

Hz

m

s

pH

ST

g/h

MT/min

lb/ h

g/cm3

g/l

Nm3/h

MJ/h

MPa

No.

3

7

11

15

19

23

27

31

35

39

43

47

51

55

59

63

67

71

Unit

mmH2O

mbar

kPa

m3/h

mA

cm

h

kg

LT

kg/s

MT/h

ST/min

kg/m3

m/h

Nm3/min

MJ

None

No.

4

8

12

16

20

24

28

32

36

40

44

48

52

56

60

64

68

72

Unit

mmHg

g/cm2

torr

m/s

mv

L

mm

%

MT

g/s

kg/min

lb/s

ST/h

g/ml

m3/min

KJ/h

GJ/h

No

24

Appendix II: various types of equipment menu tree

Pressure Transmitter menu tree:

25

Electromagnetic Flowmeter menu tree:

26

Vortex Flowmeter menu tree:

27

Target Flowmeter / float level gauge menu tree:

28

Gold transfer meter menu tree:

29

Common menu tree:

30

Appendix 3: Glossary

Alphanumeric

Alphanumeric character set, often including other character sets,

such as punctuation marks.

Device configuration

Define the physical properties and operating characteristics of

the device parameters. Does not include dynamic data.

Device Description

Written in the HART Foundation fieldbus devices instruction set,

the device description language of the host application and the

HART or FOUNDATION fieldbus device communication

parameters, and methods of instruction are defined.

Field Equipment

In addition to HART digital communication signal, the field

device can generate or receive analog signals.

HART devices

Using the HART protocol for information communication

equipment.

HART Loop

One communication network, the master and slave devices are

HART smart or HART compatible devices.

HART protocol

Addressing a high-speed remote communications protocol

converter. One for the digital add-type 4-20mA communications

and intelligent field devices, industry-standard protocols.

Poll

One kind of query the network in order to determine the method

that the device online.

31